Product Detail

Model No.: FUD-3I-3U
Production Capacity: 2000pcs/month
Delivery Date: with in 10 days
standard: GB/T 13850-1998, IEC688:199...
Input range: AC 0-10A ,AC 0-500V(Option)...
Storage conditions: Temperature: -40 to +70℃ RH...
Means of Transport: Ocean,Land,Air
Packing: EXPORT CARTON
cetification: iso9001
Accuracy: 0.2%, 0.5%
Dimension: 110mm x 75mm x 120mm
Working environment: Temperature: -10 to +50℃ RH...

Excellent temperature characteristic.
Good working stability,Configuration compactness and briefness.
Change the AC current/voltage to the DC.

Introduction:

Change the measured AC current/voltage to the DC current/voltage output according to the 

linear scale.Excellent temperature characteristic and good working stability.

Configuration compactness and briefness.


Features:

1. Three phase current / voltage transducer

2. AC current / voltage transducer

3. Accuracy class can reach 0.2%

4. AC input range can be customized

5. DC output range can be customized


Model Description:

 

FUD-Type-Input-Power Supply-Output
Type3I: Three phase AC current transducer
3U: Three phase AC voltage transducer

AC inputA1: 0-1A, A2: 0-5A, A3: 0-10A.
V0: 0-70V, V1: 0-120V, V2: 0-250V,
V3: 0-300V, V4: 0-450V, V5: 0-500V.

Power supplyP1: AC110V±10%, P2: AC220V±15%, P3: AC110V-330V.
DC outputO1: 0-5V, O2: 1-5V, O3: 0-20mA, O4: 4-20mA, O5: RS485.
Example 1: FUD-3I-A2-P2-O4
FUD series three phase AC current transducerInput: AC 0-5A
Power supply: AC220V±15%
Output: DC4-20mA
Example 2: FUD-3U-V2-P2-O4




FUD series three phase AC voltage transducerInput: AC 0-250V
Power supply: AC220V±15%
Output: DC4-20mA
Please check the type, input range, output range and power supply when your order the product.


Technical Index

Technical Index
StandardGB/T 13850-1998, IEC688:1992
Accuracy0.2%, 0.5%
Consumption≤3VA
Accuracy driftAnnual variation < 0.2%
Insulation voltageAC 2kV/min.1mA (Between input- output / power)
Insulation resistance≥20MΩ (DC500V)
Surge voltage5KV (Peak value), 1.2/50μs
Response time≤350ms
Input rangeAC 0-10A ,AC 0-500V(Option), 50/60Hz
Absorbed power<0.5VA/450V, <0.2VA/100V, <0.1VA/5A
OverloadCurrent: 2 times continuous, 30 times /1s; 
Voltage: 2 times continuous
Load resistanceCurrent output: RL≤550Ω
Voltage output: RL≥2kΩ
Working environmentTemperature: -10 to +50℃
RH: 20-90%, without condensation
Storage conditionsTemperature: -40 to +70℃
RH: 20-95%, without condensation
Installation35mm DIN sliding-way or M4 screws
Dimension110mm x 75mm x 120mm


bigPhoto
 Ms. cissychen
sales
Tel: 86-10-85583577
Fax: 86-10-85781298
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Beijing GFUVE Electronics Co.,Ltd [China (Mainland)]


Business Type:Manufacturer, Trading Company
City: Beijing
Province/State: Beijing
Country/Region: China (Mainland)

You May Like: